The following section lists additional status codes and messages that may appear on your libbi. Each one indicates a specific operating condition or issue that may require further attention.

WARNING

DO NOT attempt to complete any actions which are labeled "INSTALLER ONLY", unless you are a qualified installer or electrician. 

Status Code Meaning Status or Action Action (If Required)
Code 51: Max Charge Grid Limit Charge limited by grid limit or exceeded in stop mode. Status Only No action required unless unexpected. Review settings.
Code 52: Max Drain Grid Limit Discharge limited by grid limit. Status Only Review settings if unexpected.
Code 53: Max Charge Device Limit Charge limited by device limit. Status Only Check device limit configuration.
Code 54: Max Drain Device Limit Discharge limited by device limit. Status Only Check device limit configuration.
Code 55: Max Charge Group Limit Charge limited by a group limit, can show in stop mode. Status Only Review group limits.
Code 56: Max Drain Group Limit Discharge limited by a group limit. Status Only Review group limits.
Code 57: harvi Lost Comms

harvi not heard from for 24 hours+.

 

Action Required Check harvi is still flashing green and has a clear connection to the libbi controller.
Code 58: Generation CT Polarity Generation CT polarity reversed. Action Required INSTALLER ONLY: Correct CT orientation.
Code 101: Battery Empty Minimum state of charge reached. Status Only N/A
Code 102: Battery Full Maximum state of charge reached. Status Only N/A
Code 106: Grid CT Lost Grid readings lost, device stopped for safety. Action Required INSTALLER ONLY: Check grid CT connected to controller.
Code 107: Master Lost Load control master device lost, device stopped for safety. Action Required Ensure master is powered. Check pairing and channel.
Code 183: Inv Comms LostCode 183: Inv Comms Lost Controller–inverter comms lost. Action Required INSTALLER ONLY: Check RS485 present, polarity at controller, and cable integrity.
Code 184: Controller Undervoltage Low grid voltage at controller. Action Required Contact DNO/Installer to check voltages
Code 185: Controller Overvoltage

High grid voltage at controller.

Action Required Contact DNO/Installer to check voltages
Code 186: Controller Under Frequency Low grid frequency at controller. Action Required Contact DNO/Installer to check voltages
Code 187: Controller Over FrequencyCode 187: Controller Over Frequency High grid frequency at controller. Action Required Contact DNO/Installer to check voltages
Code 201 / F00: Soft Time Out Internal soft timeout. Action Required Reboot libbi
Code 202 / F01: INV Volt Short

Internal voltage short event.

Action Required Reboot libbi
Code 203 / F02: GFCI Sensor Fault GFCI sensor fault. Action Required Reboot libbi
Code 205 / F04: Bus Volt Low DC bus voltage low. Action Required Reboot libbi
Code 206 / F05: Bus Volt High DC bus voltage high. Action Required Reboot libbi
Code 207 / F06: Bus Short Circuit

DC bus short event.

Action Required Reboot libbi
Code 208 / F07: PV ISO Under Fault PV insulation resistance low. Action Required

Reboot libbi.

INSTALLER ONLY: Check PV earth resistance and earthing quality.

Code 209 / F08: PV Input Short Circuit PV input short detected. Action Required

Use DC isolator to disconnect PV safely. Reboot. Reconnect.

INSTALLER ONLY: As above. Inspect PV strings and wiring for shorts.

Code 210 / F09: Bypass Relay Fault Bypass relay issue. Action Required

Isolate PV via DC isolator. Reboot. Reconnect.

INSTALLER ONLY: Check PV wiring for faults.

Code 211 / F10: INV Curr Over Inverter overcurrent. Action Required

Wait 5 minutes for auto-restart. Reboot if needed.

INSTALLER ONLY: Check wiring, including backup circuit.

Code 212 / F11: INV DC Over Inverter DC overvoltage. Action Required Reboot libbi
Code 213 / F12: Ambient Over Temp Ambient temperature too high. Action Required Improve airflow. Allow to cool. Reboot.
Code 214 / F13: Sink Over Temp Heatsink temperature too high. Action Required Improve airflow. Allow to cool. Reboot.
Code 215 / F14: Grid Relay Fault Grid relay issue. Action Required

Isolate PV via DC isolator. Reboot. Reconnect.

INSTALLER ONLY: Isolate PV via DC isolator. Reboot. Reconnect.

Code 216 / F15: DisChg Curr Over

Discharge overcurrent.

 

Action Required

Wait 1 minute for auto-restart. Reboot if needed.

INSTALLER ONLY: Check wiring, including backup circuit.

Code 217 / F16: Chg Curr Over Charge overcurrent. Action Required INSTALLER ONLY: Check for short at battery wiring port.
Code 218 / F17: Current Sensor Fault Internal current sensor fault. Action Required Contact myenergi Technical Support
Code 219 / F18: INV Abnormal Inverter abnormal state. Action Required Contact myenergi Technical Support